Techno Plus 3000VA
- Personal Computer, Modem, Local Area Networks Video Surveillance Systems
- Automatic Voltage Regulation circuit (AVR) • Output sockets for blackout protection
- Output sockets for overvoltage protection
- Cold start function
- Compatible generators
| Model |
TC2000Li |
TC2400Li |
TC3000Li |
| Capacity (VA/Watts) |
2000 / 1200 |
2400/ 1440 |
3000 / 1800 |
| INPUT | |||
| Nominal Input Voltage |
110/120Vac or 220/230/240 Vac |
||
| Operating Voltage Range |
81-145Vac/162-290 Vac |
||
| Operating Frequency Range |
50/60 Hz (1±10%) |
||
| OUTPUT | |||
| Output Voltage range (Batt. Mode) |
Simulated Sinewave at nominal voltage ±10% |
||
| Frequency Range (Batt. Mode) |
50 Hz or 60 Hz ± 1 Hz |
||
| Transfer Time |
Typical 2-6 ms, 10ms max. |
||
| BATTERY | |||
| Battery Type & Number |
12 V / 9 Ah x 2 |
12 V / 7.2 Ah x 4 |
12 V / 9 Ah x 4 |
| Typical Recharge Time |
6-8 hours ( To 90% capacity) |
||
| PROTECTION | |||
| Full Protection |
Overload and overcharge protection |
||
| INDICATORS | |||
| Indicators |
AC Mode, Battery Mode, Load Level, Battery Level |
||
| ALARM | |||
| Battery Mode |
Sounding every 10 seconds |
||
| Battery Low |
Sounding every second |
||
| Overload |
Sounding every 0.5 second |
||
| Battery Replacement Alarm |
Sounding every 2 seconds |
||
| Fault |
Continuously sounding |
||
| Management | |||
| USB & RS-232 port (Optional) |
USB or RS232(Supports Windows ,Linux, Unix, and MAC) |
||
| LCD |
UPS status, input/output voltage, input/output frequency, load level, battery capacity, and warning or fault error code. |
||
| Environment | |||
| Operating Temperature |
0- 40°C |
||
| Humidity Range |
0-95 % (Non-condensing) |
||
| Noise Level |
<45db (1 meter from surface) |
||
| PHYSICAL | |||
| Dimension, W x D x H (mm) |
158×380×198 |
144×432.5×207 |
|
| Net Weight (kg) |
10.5 |
20 |
23 |
| STANDARDS | |||
| Safety |
IEC/EN62040-1;IEC/EN60950-1 |
||
| EMC |
IEC/EN62040-2;IEC61000-4-2;IEC61000-4-3;IEC61000-4-4;IEC61000-4-5;IEC61000-4-6;IEC61000-4-8 |
||